Alteration review
Historical Commission
Outcome, as read from the minutes:ApprovedRead from the minutes by software. How to read this
Recorded conditions
Applicant to present alternatives for mechanical system based on higher summer temperature and RH boundaries and winter RH boundaries for minimizing condensation; options include state-of-the-art air handling using existing duct chases, new controls with existing and new chases where non-consequential to historic fabric, or develop proposed system with new boundaries; detail of design for proposed air intake louvers required; sufficient technical evidence required that ground-level louvers are necessary with detail of louvers if approved; Applicant to provide technical rationale for replacing basement windows with intake/exhaust louvers
Prior meeting reference: Architectural Committee Special Meeting, 10 April 1994
- Vote tally How to read this
- unanimous
- Criteria cited
- Electrical system compatibilityFire protection system compatibilitySecurity system compatibilityHistoric fabric preservation